Plan Review Notes For Permit 18070895 |
Permit Number |
18070895 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-25 12:27:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) SHEET A 501 - THE IS A WOOD TRUSS SYSTEM INDICATED | | OVER THE BAR AREA. THERE IS AN EXISITNG FIRE SPRINKLER | | SYSTEM IN PLACE OVER THESE PROPOSED TRUSSES. THESES | | TRUSSES ARE AN OBSTRUCTION TO THE EXISITNG SYSTEM. | | | | THERE ARE NO INDICATIONS ON ANY PLAN SHEET TO PROVIDE | | FIRE SPRINKLER PROTECTION UNDER THESE TRUSSES. | | | | FIRE SPRINKLER PROTECTION IS REQUIRED. | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC | | DETAILS AND CODE EFERENCES. | | | | | | | | | | 2) SHEET A 201 - THERE ARE BAR STOOLS INDICATED ALONG | | THE BAR AREA WITH NO LINEAR DIMENSIONS. | | | | PLEASE PROVIDE THE APPLICABLE DIMENSIONS FOR THE LINEAR | | BAR AND BARSTOOL SEPARATION. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|