2018-07-25 12:27:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 501 - THE IS A WOOD TRUSS SYSTEM INDICATED
 OVER THE BAR AREA. THERE IS AN EXISITNG FIRE SPRINKLER
 SYSTEM IN PLACE OVER THESE PROPOSED TRUSSES. THESES
 TRUSSES ARE AN OBSTRUCTION TO THE EXISITNG SYSTEM.
  
 THERE ARE NO INDICATIONS ON ANY PLAN SHEET TO PROVIDE
 FIRE SPRINKLER PROTECTION UNDER THESE TRUSSES.
  
 FIRE SPRINKLER PROTECTION IS REQUIRED.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAILS AND CODE EFERENCES.
  
  
  
  
 2) SHEET A 201 - THERE ARE BAR STOOLS INDICATED ALONG
 THE BAR AREA WITH NO LINEAR DIMENSIONS.
  
 PLEASE PROVIDE THE APPLICABLE DIMENSIONS FOR THE LINEAR
 BAR AND BARSTOOL SEPARATION.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  