Plan Review Notes
Plan Review Notes For Permit 18070830
Permit Number 18070830
Review Stop E
Sequence Number 1
Notes
Date Text
2018-07-27 07:09:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. SHOW CONDUIT SIZE,
 PATH OF CONDUITS, WHAT PANEL THE LIFT WILL BE FED FROM,
 LOAD CALCULATION FOR THE PANEL, OVER CURRENT
 PROTECTION, ETC. FS 471.003(2)(H); 471.025; WPB FBC
 107.2.1, 107.3.5
  
 2. CONFLICTING INFORMATION ABOUT MOTORS ON PLAN. SHOWS
 BOTH 2X- 3/4HP MOTORS ON PLAN AND ALSO 2X- 1-1/2HP
 MOTORS ON PLAN, PLEASE CLARIFY.
  
 3. PROVIDE SUBMITTALS FOR BOAT MOTORS FOR PRODUCT
 APPROVAL. MUST BE NRTL/UL LISTED. FBC 107.2.1, 110.3B
 NEC
  
 4. ADDRESS OF PROJECT MUST BE ON PLAN. FBC 107.2.1
  
 INFORMATIONAL NOTE: PLEASE SPEAK WITH BUILDING
 INSPECTORS AND ENGINEERING ABOUT PENETRATIONS THROUGH
 SEA-WALL AND CONDUIT BEING RAN THROUGH CITY EASEMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  