2018-07-27 07:09:05 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| ELECTRICAL CONTRACTOR QUALIFIER. SHOW CONDUIT SIZE, |
| PATH OF CONDUITS, WHAT PANEL THE LIFT WILL BE FED FROM, |
| LOAD CALCULATION FOR THE PANEL, OVER CURRENT |
| PROTECTION, ETC. FS 471.003(2)(H); 471.025; WPB FBC |
| 107.2.1, 107.3.5 |
| |
| 2. CONFLICTING INFORMATION ABOUT MOTORS ON PLAN. SHOWS |
| BOTH 2X- 3/4HP MOTORS ON PLAN AND ALSO 2X- 1-1/2HP |
| MOTORS ON PLAN, PLEASE CLARIFY. |
| |
| 3. PROVIDE SUBMITTALS FOR BOAT MOTORS FOR PRODUCT |
| APPROVAL. MUST BE NRTL/UL LISTED. FBC 107.2.1, 110.3B |
| NEC |
| |
| 4. ADDRESS OF PROJECT MUST BE ON PLAN. FBC 107.2.1 |
| |
| INFORMATIONAL NOTE: PLEASE SPEAK WITH BUILDING |
| INSPECTORS AND ENGINEERING ABOUT PENETRATIONS THROUGH |
| SEA-WALL AND CONDUIT BEING RAN THROUGH CITY EASEMENTS. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |