2018-08-10 16:48:321ST REVIEW FBC-2010 MECHANICAL
 REVISION #18070821
 PERMIT #15111020
 8/10/18
  
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2-90-15A: PLEASE IDENTIFY THE DUCTS THAT ARE
 PENETRATING THE FIRE-RATED LAUNDRY/CORE COMMON WALLS.
 SHOW DUCT SIZES AND DAMPER SYMBOLS AT THE PENETRATIONS.
  
 2) M2-90A-15A: IT DOES NOT APPEAR THAT ALL AIR FROM THE
 MASTER SUITES, INCLUDING THE CLOSETS AND BATHS, IS
 BEING RETURNED AS REQUIRED BY SECTION 601.4 (3).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  