Plan Review Notes For Permit 18070821 |
Permit Number |
18070821 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-10 16:48:32 | 1ST REVIEW FBC-2010 MECHANICAL | | REVISION #18070821 | | PERMIT #15111020 | | 8/10/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2-90-15A: PLEASE IDENTIFY THE DUCTS THAT ARE | | PENETRATING THE FIRE-RATED LAUNDRY/CORE COMMON WALLS. | | SHOW DUCT SIZES AND DAMPER SYMBOLS AT THE PENETRATIONS. | | | | 2) M2-90A-15A: IT DOES NOT APPEAR THAT ALL AIR FROM THE | | MASTER SUITES, INCLUDING THE CLOSETS AND BATHS, IS | | BEING RETURNED AS REQUIRED BY SECTION 601.4 (3). | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|