2018-09-27 17:23:05FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NOTHING IN THE PAPER WORK SHOWS THE REQUIRED GF
 PROTECTION 690.5, AND ARC FAULT PROTECTION 690.11 FOR
 THE CONTROLLER.
  
 ALSO NEED TO KNOW HOW POOL IS TO BE BONDED??? 680.26,
 IS THERE AC POWER IN THE POOL? LIGHT? CLORINATOR?
  
 PLEASE SUBMIT DIAGRAM SHOWING ALL POOL EQUIPMENT.
  
  