2018-08-29 13:41:36FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 I MISSED THAT THIS WAS A POOL PUMP FIRST TIME AROUND.
  
 I WILL NEED THE CUTSHEETS FOR THE CONTROLER AND PUMP
 SHOWING THAT IT IS LISTED FOR USE WITH A POOL.
  
 690.5 REQUIRES GF PROTECTION
 690.11 REQUIRES ARC FAULT PROTECTION
  
 COULD NOT FIND PS800 CONTROLER.