Plan Review Notes For Permit 18070813 |
Permit Number |
18070813 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-31 09:15:55 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ENGINEER'S ROOF PRESSURE DRAWINGS ON SHEET S-1 | | SHOWS THE SOLAR POOL HEATER PANELS LOCATED IN ROOF ZONE | | 2 WITH AN UPLIFT PRESSURE OF -66.31 PSF. THE 4" LAG | | BOLTS WITH 3.5 INCHES OF THREAD HAVE A MAXIMUM PRESSURE | | OF 65 PSF. FBC-R301.2.1 | | | | 2) THE SIZE OF THE PANELS THAT WILL BE INSTALL HAS NOT | | BEEN PROVIDED. FBC-R107.2.1 | | | | 3) THE SPACING OF THE TOP HEADER ANCHORS IS NOT | | SPECIFIED. FBC-R 301.1 | | | | 4) THE ANCHORING OF THE BOTTOM HEADER AND THE | | SUPPLY/RETURN PIPING WAS NOT SPECIFIED. FBC-R301.1 |
|