Plan Review Notes For Permit 18070766 |
Permit Number |
18070766 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-28 03:16:34 | 1) GAS FIRED POOL HEATERS SHALL HAVE A MINIMUM THERMAL | | EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC. | | R403.10.4. THE SUBMITTED SPECS DO NOT SHOW THIS. | | 2) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS | | MUST INCLUDE ALL OF THE SYSTEM COMPONENTS IN THE PIPING | | SYSTEM INCLUDING THE FILTER. | | 3) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE. | | IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC | | TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS | | NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH | | CALCULATIONS. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|