Plan Review Notes
Plan Review Notes For Permit 18070686
Permit Number 18070686
Review Stop Z
Sequence Number 1
Notes
Date Text
2018-07-23 16:59:50************************************ZONING REVIEW FAILE
 D**************************************************
  
 ENGINEERING COMMENTS ON EXPANSION OF PURITAN ROAD MUST
 BE SATISFIED PRIOR TO APPROVAL OF THIS BUILDING PERMIT.
  
 APPROVAL OF SUBDIVISION APPLICATION MUST BE OBTAINED
 PRIOR TO APPROVAL FOR THIS BUILDING PERMIT.
  
 THE FRONT SETBACK IN THE SF-14 DISTRICT IS A MINIMUM OF
 25 FEET.
  
 A 3 FOOT SETBACK FOR THE DRIVEWAY IS REQUIRED FROM SIDE
 PROPERTYLINES.
  
 INDICATE THE HEIGHT OF THE PROPOSED STRUCTURES ON THE
 ELEVATION DRAWINGS.
  
 DIMENSION SETBACKS. MECHANICAL EQUIPMENT. MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK. WINDOW AIR-CONDITIONING UNITS MAY NOT PROJECT
 MORE THAN 18 INCHES INTO A REQUIRED SIDE SETBACK.
  
 DIMENSION OVERHANGS. STRUCTURAL INTRUSIONS. STRUCTURAL
 OVERHANGS, INCLUDING BUT NOT LIMITED TO BALCONIES,
 CORNICES, GUTTERS, EAVES, AND ROOF OVERHANG PROJECTIONS
 SHALL NOT EXTEND FARTHER THAN THREE FEET INTO ANY
 SETBACK.
  
 SEPARATE PERMITS ARE REQUIRED FOR FENCES/WALSL,
 GENERATORS, POOLS, DRIVEWAYS, LANDSCAPING, IRRIGATION,
 AND MECHANICAL/AC/POOL EQUIPMENT,
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A.
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  
  