Plan Review Notes
Plan Review Notes For Permit 18070665
Permit Number 18070665
Review Stop B
Sequence Number 1
Notes
Date Text
2018-07-24 09:24:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED
 REQUIRES THE 16KW GENERATOR TO HAVE A MINIMUM WEIGHT OF
 448 POUNDS. THE GENERATOR THAT IS PROPOSED HAS A UNIT
 WEIGHT OF 409 POUNDS WHICH DOES NOT MEET THE MINIMUM
 REQUIRED. FBCR-G2404.6