2018-07-31 11:44:51 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18070655 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC EB = FBC EXISTING BUILDING |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC 109]PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO |
| SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT |
| APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL COST OF |
| WORK. VALUE WILL BE FOR ALL WORK INCLUDING MECHANICAL |
| AND ELECTRICAL. |
| |
| 2. [FBC 107.2.5]HEAD AND SILL DETAIL ARE FOR WOOD FRAME |
| 2X6. PROVIDE DETAILS FOR SITE CONDITIONS(2X4 |
| CONSTRUCTION AND MASONRY CONSTRUCTION). |
| ALSO, BUCK DETAILS FOR BOTH CONDITIONS. |
| |
| 3. [FBC 107.2.5]PROVIDE INFILL DETAILS IF OPENINGS ARE |
| BEING ADJUSTED. |
| |
| 4. [FBC 107.2.5]THE WINDOW PRODUCT APPROVAL ALLOWS FOR |
| OPENINGS UP TO 52". |
| PLEASE ADJUST WINDOWS TO MEET PRODUCT APPROVAL. I WOULD |
| SUGGEST A WINDOW SCHEDULE. SELECT WINDOW TYPE FOR WALL |
| TYPE (NAIL FIN OR THROUGH FRAME, IF WINDOW IS EGRESS, |
| PROVIDE BOTH R.O. AND WINDOW SIZE FOR EACH |
| WINDOW.(WINDOW SCHEDULE) |
| |
| 5. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN |
| EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW |
| FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE |
| REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE |
| REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE |
| R402.1.2. |
| YOUR WINDOWS SHOULD HAVE U-FACTOR OF 0.75 AND SHGC OF |
| 0.25THE WINDOWS SHOULD COME WITH STICKERS ON THEM. |
| LEAVE THE STICKERS ON WINDOWS UNTIL YOU PASS |
| INSPECTION. |
| |
| 6. [FBC R317.1] 5.WOOD SIDING, SHEATHING AND WALL |
| FRAMING ON THE EXTERIOR OF A BUILDING HAVING A |
| CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE |
| GROUND OR LESS THAN 2 INCHES (51 MM) MEASURED |
| VERTICALLY FROM CONCRETE STEPS, PORCH SLABS, PATIO |
| SLABS AND SIMILAR HORIZONTAL SURFACES EXPOSED TO THE |
| WEATHER. |
| |
| 7. WHEN RE-SUBMITTING HAVE THE PERMIT APPLICATION |
| NOTARIZED. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |