2018-07-23 16:42:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION ADDRESSES
 FLOW RATE IN GALLONS PER MINUTE (GPM). IT REQUIRES THAT
 MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED
 MAXIMUM FLOW RATE OF THE SUCTION OUTLET FITTING
 ASSEMBLY (DRAIN COVER).
  
 2) INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS
 APPLICABLE TO THE SPECIFIC PUMP BEING INSTALLED ON THIS
 SYSTEM. THIS IS REQUIRED TO MATCH THE CALCULATED TDH TO
 THE MAXIMUM SYSTEM FLOW RATE OF THE SYSTEM ON THE PUMP
 CURVE.
  
  