Plan Review Notes
Plan Review Notes For Permit 18070628
Permit Number 18070628
Review Stop P
Sequence Number 1
Notes
Date Text
2018-07-17 15:19:3807/17/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE WASHER AND DRYERS INSTALLATION MANUAL AND
 SHOW EXISTING LOCATION OF UNIT AND VERIFY ACCESS TO
 SHUT-OFF VALVE LOCATION. FBC 107.3.5
  
 2) AAV'S ARE NOT PERMITTED ON A 2" HORIZONTAL BUILDING
 DRAIN. FBC 303.2
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]