2018-07-18 12:36:26RESIDENTIAL (R3) PARTIAL RE-ROOF BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLINTLASTIC SELF-ADHERING ROOFING SYSTEM NOA
 15-0622.21 IS NOT AN UNDERLAYMENT FOR ROOF CLAY TILE
 INSTALLATION. THIS IS A ROOFING SYSTEM FOR FLAT ROOFS.
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR UNDERLAYMENT
 SYSTEM THAT IS DESIGNED FOR ROOF CLAY TILE
 INSTALLATION. FAC 61G20-3.001.
 CLEARLY IDENTIFY WHICH APPROVED UNDERLAYMENT SYSTEM IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. ,
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
  