2018-08-21 07:04:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALC NOT TO NEC 220.84 REQUIREMENTS. DEMAND
 FACTOR OF 45% IS ONLY APPLIED ONE TIME TO THE ENTIRE
 LOAD. SQUARE FOOTAGE FOR APARTMENTS IS 24,984 BUT VA IS
 24,984 ALSO???
  
 END OF COMMENTS.
  