2018-08-10 07:19:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INACCURATE LOAD CALCULATION. NO HOUSE LOAD INCLUDED
 IN CALCULATION. ACTUAL CALCULATED LOAD (NOT INCLUDING
 HOUSE LOAD BECAUSE IT WAS NOT PROVIDED) IS 320AMPS NOT
 292AMPS. PLEASE SEE MULTI-FAMILY DWELLING LOAD CALC
 REQUIREMENTS 220.84 B&C NEC AND TABLE 220.84 NEC
  
 2. SHOW EXISING WIRE SIZE TO FPL TRANSFORMER TO VERIFY
 IT CAN SUPPORT THE LOAD. NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1
  
  
  
 END OF COMMENTS.
  