Plan Review Notes
Plan Review Notes For Permit 18070522
Permit Number 18070522
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-29 12:21:55BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS
  
 1- COMBINING TWO ADJACENT UNITS REQUIRES A UNITY OF
 TITLE:
  
 A UNITY OF TITLE IS REQUIRED. SUBMIT APPLICATION TO THE
 ENGINEERING DEPARTMENT:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 NOTE:
 IF THIS HAS ALREADY BEEN DONE, PLEASE PROVIDE A COPY OF
 THE RECORDED DOCUMENT.
  
  
 2- ENGINEER'S LETTER SUBMITTED REGARDING NEW OPENING IN
 EXISTING CAST IN PLACE CONCRETE SHEARWALL:
 A) SCOPE OF WORK INCLUDES ALTERATION OF THE STRUCTURAL
 DESIGN OF THE BUILDING. ENGINEER'S LETTER SUBMITTED IS
 TOO GENERAL. ENGINEER'S STATEMENT SHALL EITHER A)
 COMPARE THE REMAINING SHEARWALL AREA AT THIS FLOOR TO
 THE SHEARWALL AREA OF THE LOWER FLOOR OR B) GIVE SOME
 OTHER FORM OF JUSTIFICATION FOR REDUCING SHEAR WALL
 AREA. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 B) ENGINEER'S LETTER NEED TO HAVE COMPLETE AND CORRECT
 ADDRESS. SEC. 107.2.1 CITY AMENDMENTS. THIS BUILDING IS
 NOT LOCATED IN MIAMI, FLORIDA. THE CORRECT ADDRESS IS
 550 OKEECHOBEE BLVD UNITS 727 AND 728, WEST PALM BEACH,
 FLORIDA 33401.
  
 C) ENGINEER'S LETTER NEEDS ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS.
  
 3- FLOORING SOUND INSULATION INFORMATION ON SHEET
 A-1.1: ARCHITECT IS SPECIFYING IMPACT INSULATION (71
 DB) AND SOUND TRANSMISSION CONTACT (71 DB). TYPICALLY
 THIS RATING IS ONLY ACQUIRED WHEN USING SOUND
 INSULATION ASSEMBLIES THAT HAVE A SUSPENDED ACOUSTICAL
 CEILING. SEE TEST REPORTS. TYPICALLY BUILDINGS IN THIS
 AREA DON'T HAVE THE SUSPENDED ACOUSTICAL CEILING IN ALL
 AREAS. AND, ACCORDING TO CITY RECORDS, THIS BUILDING
 DOESN'T HAVE A SUSPENDED ACOUSTICAL CEILING THROUGHOUT
 THE APARTMENT. REVISE SPECIFICATIONS AS REQUIRED. THE
 MIN DB REQUIRED BY THE CODE IS 50DB. SEC. 1207.2 AND
 1207.3 FBC..
  
 4- FLOORING SOUND INSULATION MATERIAL. (NOTE: THIS MAY
 BE SUBMITTED LATER BEFORE INSTALLATION AS A DEFERRED
 SUBMITTAL):
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
  
 4- THIS IS A THRESHOLD BUILDING AND THE SCOPE OF WORK
 INCLUDES ALTERATION OF THE STRUCTURAL DESIGN OF THE
 BUILDING. SPECIAL INSPECTOR WILL BE REQUIRED FOR
 INSPECTIONS AT THE SHEARWALL. SEC. 110.8 CITY
 AMENDMENTS.
 NOTE: PLEASE CONTACT THIS OFFICE WHEN CONTRACTOR IS
 SELECTED FOR SPECIAL INSPECTOR PROCEDURE.
  
 5- THRESHOLD BUILDING: ONLY GENERAL CONTRACTOR CAN DO
 STRUCTURAL WORK. SEC. 110.3.7.5 CITY AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION