2018-08-01 06:06:43 | 1) THE POOL PLANS SHOW TDH CALCULATIONS BASED ON THE | | SIMPLIFIED TDH CALCULATION METHOD. THIS METHOD IS | | ALLOWED IN THE 2006 VERSION OF APSP 7 BUT IS NO LONGER | | ALLOWED IN THE 2013 EDITION OF APSP 7 WHICH HAS BEEN | | ADOPTED BY THE 2017. | | FBC. TOTAL DYNAMIC HEAD CALCULATIONS SHALL BE DONE IN | | ACCORDANCE WITH 2013 APSP 7 SEC.4.4.9.1. | | 2) THE GAS POOL HEATER SHALL HAVE A MINIMUM THERMAL | | EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY | | SEC.R403.10.4. | | 3) TWO PUMP CURVES HAVE BEEN PROVIDED BUT THERE IS NO | | INDICATION ON EITHER CURVE WHICH CURVE KEY IS SPECIFIC | | TO THE TDH CALCULATIONS. THERE ARE DIFFERENT RPM'S ON | | THE CURVES. CLARRIFY WHICH ONE. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|