2018-07-23 08:50:201) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW FOR THE POOL, THE SPA AND THE POOL
 FEATURE. THE MAXIMUM FLOW OF THE PUMP FROM ITS PUMP
 CURVE IS NO LONGER ALLOWED TO BE USED IN DETERMINING
 MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC 7 - 2013
 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION ADDRESSES FLOW
 RATE IN GALLONS PER MINUTE (GPM). IT REQUIRES THAT
 MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED
 MAXIMUM FLOW RATE OF THE SUCTION OUTLET FITTING
 ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS MUST
 INCLUDE ALL OF THE SYSTEM COMPONENTS IN THE PIPING
 SYSTEM INCLUDING THE FILTER.
 2) SUBMIT TWO COPIES OF THE POOL PUMP CURVE FOR THE
 POOL, THE SPA AND POOL FEATURE. IDENTIFY ON THE PUMP
 CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING
 INSTALLED ON THESE ITEMS. THIS IS NEEDED TO CONFIRM THE
 MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS.
 3) INDICATE ON THE POOL PUMP SPECS WHICH PUMP IS BEING
 INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
 4) BACKFLOW PREVENTERS MAY BE REQUIRED ON THE
 WATER/FIRE BOWL UNITS.
 5) THE GAS HEATER SHALL HAVE A MINIMUM OF 82%
 EFFICIENCY PER THE 2017 FBC-ENERGY TABLE C404.2. SUBMIT
 VERIFICATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692