Plan Review Notes
Plan Review Notes For Permit 18070315
Permit Number 18070315
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-10 07:09:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PLEASE CONTACT ME IF YOU WANT ASSISTANCE WITH
 SUBMITTING.
  
 2. DELEGATED ENGINEERING WAS SUBMITTED.
  
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS.
 2017 FBC-B 2204.1 WELDING, 2204.2 BOLTING.
  
 PROVIDE INFORMATION AS TO WHO WILL BE PERFORMING THESE
 INSPECTIONS. REVISE PLAN TO CLARIFY INSTALLATION
 LOCATION.
  
 3. OK
  
 4. NOAS WERE SUBMITTED AS INDIVIDUAL PAGES. ALL PRODUCT
 APPROVALS SHOULD BE UPLOADED AS ONE PDF INTO
 "SUPPORTING DOCUMENTS" FOLDER.
  
 2ND REVIEW - THE NUMEROUS INDIVIDUAL PAGES HAVE BEEN
 DELETED FOR YOU. THE NEW DOCUMENT NAMED "NOA PDF.PDF"
 INCLUDES THE FIRST TWO NOA PAGES UPSIDE DOWN, THEN
 DELEGATED ENGINEERING SHOP DRAWINGS (WHICH WERE ALSO
 INCLUDED IN THE DRAWINGS FOLDER), THEN WHAT APPEARS TO
 BE PAGES FROM A FLORIDA STATE PRODUCT APPROVAL.
  
 PROVIDE A CLEAN PRODUCT APPROVAL; EITHER NOA OR FLORIDA
 STATE PRODUCT APPROVAL IS ACCEPTABLE. IF USING A
 FLORIDA STATE PRODUCT APPROVAL, INCLUDE THE COVER PAGE
 WHICH SHOWS THE STATUS AND OTHER INFORMATION
 (WWW.FLORIDABUILDING.ORG). IF USING A NOA, INCLUDE TH
 ENTIRE DOCUMENT, IN ORDER. ALL PAGES SHOULD BE IN
 PORTRAIT ORIENTATION.
  
 FILES SHOULD BE NAMED IN A LOGICAL NAMING CONVENTION.
 THE NOA PAGES WHICH I DELETED HAD COMPUTER GENERATED
 NAMES (APPEARED TO BE SCANS) WHICH WERE ARBITRARY.
  
 IF YOU ARE UNABLE TO FOLLOW DIGITAL SUBMITTAL
 PROCEDURES, PLEASE CONVERT THIS SUBMITTAL TO PAPER.
 DIGITAL SUBMITTALS ARE SUITED TO DIGITAL DOCUMENTS. IT
 APPEARS THAT THESE DOCUMENTS WERE ORIGINALLY DIGITAL,
 PRINTED, SCANNED, UPLOADED. THIS IS RESULT IN DIFFICULT
 TO READ DOCUMENTS.
  
 WE DISCUSSED HAVING THE WINDOW DELEGATED ENGINEERING
 REMOVED BECAUSE IT DUPLICATES THE PRODUCT APPROVAL. IN
 REVIEWING, THE DELEGATED ENGINEERING ALSO INCLUDES
 OTHER DETAILS WHICH ARE NOT IN THE PRODUCT APPROVAL AND
 ARE SITE SPECIFIC. THESE DOCUMENTS ARE NEEDED FOR
 INSPECTIONS.
  
 IF YOU CHOOSE TO KEEP THIS SUBMITTAL DIGITAL, PLEASE
 UPLOAD THE WINDOW DELEGATED ENGINEERING AS ONE DOCUMENT
 RATHER THAN SEPARATE PAGES.
  
 5. OK
  
  
  
  
  
  