2018-07-21 15:11:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PROVIDE ROOM DESIGNATION FOR 1-100, A1.1.
  
 2. DELEGATED ENGINEERING WAS SUBMITTED.
  
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS.
 2017 FBC-B 2204.1 WELDING, 2204.2 BOLTING.
  
 PROVIDE INFORMATION AS TO WHO WILL BE PERFORMING THESE
 INSPECTIONS. REVISE PLAN TO CLARIFY INSTALLATION
 LOCATION.
  
 3. WINDOW DETAILS WERE PROVIDED. PLEASE REMOVE. ALL
 DOOR INSTALLATION DETAILS SHOULD BE INCLUDED IN THE
 PRODUCT APPROVAL, WHICH WAS NOT PROVIDED. SUPPLEMENTARY
 SHOP DRAWINGS DO NOT NEED TO BE SUBMITTED FOR REVIEW
 UNLESS THEY DEVIATE FROM THE PRODUCT APPROVAL, FBC 107.
  
 4. NOAS WERE SUBMITTED AS INDIVIDUAL PAGES. ALL PRODUCT
 APPROVALS SHOULD BE UPLOADED AS ONE PDF INTO
 "SUPPORTING DOCUMENTS" FOLDER.
  
 5. REVISE PLAN TO CLARIFY - INTERIOR AND EXTERIOR
 STOREFRONT IS PROPOSED. IS EXTERIOR STOREFRONT PROPOSED
 FOR BOTH INTERIOR AND EXTERIOR LOCATIONS?
  
  
  
  
  
  