Plan Review Notes For Permit 18070315 |
Permit Number |
18070315 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-21 15:11:45 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 107, PROVIDE ROOM DESIGNATION FOR 1-100, A1.1. | | | | 2. DELEGATED ENGINEERING WAS SUBMITTED. | | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | STANDARDS. | | 2017 FBC-B 2204.1 WELDING, 2204.2 BOLTING. | | | | PROVIDE INFORMATION AS TO WHO WILL BE PERFORMING THESE | | INSPECTIONS. REVISE PLAN TO CLARIFY INSTALLATION | | LOCATION. | | | | 3. WINDOW DETAILS WERE PROVIDED. PLEASE REMOVE. ALL | | DOOR INSTALLATION DETAILS SHOULD BE INCLUDED IN THE | | PRODUCT APPROVAL, WHICH WAS NOT PROVIDED. SUPPLEMENTARY | | SHOP DRAWINGS DO NOT NEED TO BE SUBMITTED FOR REVIEW | | UNLESS THEY DEVIATE FROM THE PRODUCT APPROVAL, FBC 107. | | | | 4. NOAS WERE SUBMITTED AS INDIVIDUAL PAGES. ALL PRODUCT | | APPROVALS SHOULD BE UPLOADED AS ONE PDF INTO | | "SUPPORTING DOCUMENTS" FOLDER. | | | | 5. REVISE PLAN TO CLARIFY - INTERIOR AND EXTERIOR | | STOREFRONT IS PROPOSED. IS EXTERIOR STOREFRONT PROPOSED | | FOR BOTH INTERIOR AND EXTERIOR LOCATIONS? | | | | | | | | | | | | |
|