Plan Review Notes For Permit 18070249 |
Permit Number |
18070249 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-24 09:47:01 | 1) THE EXISTING GAS DRAWING SHOWS A 1 INCH LINE FOR THE | | FUTURE GENERATOR AND THE THE DRAWING SUBMITTED BY | | STATIC ELECTRIC SHOWS A 3/4 INCH LINE. CLARIFY. | | 2) THE GAS LINE AT THE OUTLET OF THE GAS METER SHALL BE | | 1 1/4 INCH SCH. 40 PIPE BASED ON GAS SIZING TABLE 402.4 | | (5) AT 2 PSI AND A TOTAL DEVELOPED LENGTH OF 175 FEET | | TO THE FARTHEST REGULATOR. | | 3) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS | | FOR THE REGULATOR. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|