Plan Review Notes For Permit 18070236 |
Permit Number |
18070236 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-20 08:03:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC B 1609, PROVIDE THE MEAN ROOF HEIGHT. PROPOSED | | DESIGN PRESSURES WERE NOT PROVIDED. THIS IS REQUIRED IF | | YOU WANT FOR THE BUILDING DIVISION TO DETERMINE DESIGN | | PRESSURES. | | | | 2. REVISE APPLICATION TO INCLUDE ROOF DECK TYPE AND | | INDICATE WHICH APPROVED ASSEMBLY IS PROPOSED, FBC B | | 1609. | | | | |
|