Plan Review Notes
Plan Review Notes For Permit 18070202
Permit Number 18070202
Review Stop G
Sequence Number 2
Notes
Date Text
2018-09-21 17:40:0409/21/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE SECOND REQUEST, THE CITY RECORDS SHOW AN
 EXISTING GAS SYSTEM FOR THIS ADDRESS. THE EXISTING GAS
 DRAWING ON RECORD SHOWS A DEVELOPED LENGTH OF 60 FEET
 TO THE FARTHEST GAS OUTLET. THE SUBMITTED GAS PLAN
 SHOWS 15 FEET AS THE FARTHEST DISTANCE, PLEASE CLARIFY.
 SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP
 REGULATORS TO THE FARTHEST OUTLET. THIS DISTANCE SHALL
 BE USED IN THE SIZING OF THE LOW-PRESSURE SYSTEM.
  
 2. THE SECOND REQUEST, SUBMIT PAGES 40 & 41 OF THE GAS
 REGULATOR SPECS. THESE ARE THE INSTALLATION
 INSTRUCTIONS FOR THE REGULATORS.
  
 3. THE SECOND REQUEST, THERE ARE TWO DIFFERENT SIZING
 TABLES FOR THE PE PIPE: ONE FROM NFPA 54 AND ONE FROM
 2017 FBC-FUEL GAS. WHICH ONE IS BEING USED? REMOVE THE
 TABLE NOT BEING USED.
  
 4. THE SECOND REQUEST, THE LOCATION OF THE GENERATOR
 EXHAUST SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION MANUAL OR IF NOT SPECIFIED IN THE MANUAL,
 A MINIMUM OF 10 FEET FROM ANY BUILDING OPENINGS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  