2018-07-19 13:21:18 | |
| 1) CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS |
| ADDRESS. THE EXISTING GAS DRAWING ON RECORD SHOWS A |
| DEVELOPED LENGTH OF 60 FEET TO THE FARTHEST GAS OUTLET. |
| THE SUBMITTED GAS PLAN SHOWS 15 FEET AS THE FARTHEST |
| DISTANCE. CLARIFY. |
| 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. THE |
| EXISTING BTU LOAD SHOWN ON THE EXISTING GAS PLAN IS |
| SHOWN AS 407,000 BTU'S. |
| 3) THE SUBMITTED PLANS SHOW A 2 PSI SYSTEM AND THE |
| ORIGINAL PLANS SHOW THE EXISTING SYSTEM AS LESS THAN 2 |
| PSI. SHOW THE LOCATION OF ALL MP REGULATORS AND SHOW |
| THE DISTANCE FROM THE OUTLET OF THE GAS METER TO THE |
| FARTHEST MP REGULATOR ON THE SYSTEM. THIS DISTANCE |
| SHALL BE USED FOR THE SIZING OF THE 2 PSI SYSTEM. |
| 4) SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP |
| REGULATORS TO FARTHEST OUTLET. THIS DISTANCE SHALL BE |
| USED IN THE SIZING OF THE LOW PRESSUJRE SYSTEM. |
| 5) SUBMIT PAGES 40 & 41 OF THE GAS REGULATOR SPECS. |
| THESE ARE THE INSTALLATION INSSTRUCTIONS FOR THE |
| REGULATORS. |
| 6) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE |
| PIPE: ONE FROM NFPA 54 AND ONE FROM 2017 FBC-FUEL GAS. |
| WHICH ONE IS BEING USED? REMOVE THE TABLE NOT BEING |
| USED. |
| 7) THE LOCATION OF THE GENERATOR EXHAUST EXHAUST SHALL |
| COMPLY WITH THE MANUFACTURER'S INSTALLATION MANUAL OR |
| IF NOT SPECIFIED IN THE MANUAL, A MINIMUM OF 10 FEET |
| FROM ANY BUILDING OPENINGS. |
| |
| NOTE: FOR FUTURE GAS SUBMITTALS, ENSURE THERE ARE TWO |
| COPIES OF EACH PAGE OF THE SPECIFICATIONS IN THE |
| SUBMITTAL AND DIVIDED INTO TWO SEPARATE PACKETS. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |