Plan Review Notes
Plan Review Notes For Permit 18070134
Permit Number 18070134
Review Stop P
Sequence Number 1
Notes
Date Text
2018-07-23 13:08:211) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS IN THE PIPING
 SYSTEM INCLUDING THE FILTER.
 2) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS.
 3) INDICATE ON THE POOL PUMP SPECS WHICH PUMP IS BEING
 INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. 4 OF 4 - PLEASE REVISE NOTES #7 & #8 -
 REFERENCE IS MADE TO 2017 FBCR SEC. R 4101.6.6. THIS
 SECTION HAS NOTHING TO DO WITH SWIMMING POOLS.
 5) SHTS.1 & 2 - THERE IS A NOTE IN THE UPPER LEFT
 CORNER OF THE SHEET NOTING THAT THE POOL PIPING HAS
 BEEN DESIGNED BASED ON THE MAXIMUM FLOW CAPACITY OF THE
 SWIMMING POOL PUMP. THIS DESIGN IS NO LONGER PERMITTED
 BY APSP-7 2013.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW