Plan Review Notes
Plan Review Notes For Permit 18070117
Permit Number 18070117
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-21 13:17:48****CORRECTIONS****
 W.P.B. PERMIT: 18070117
 REVIEWED: AUGUST 20, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC R = FBC RESIDENTIAL
  
 1. [FBC R107]PROVIDE SURVEY OF PROPERTY.
  
 2. [FBC AMENDED 107]ADD ROOF PITCH TO PLANS.
  
 3. [FBC AMENDEDWHAT IS EXISTING ROOFING MATERIAL, AND
 WHAT IS PROPOSED?
  
 4. WHAT ARE THE LOADS ON NEW ROOF?
  
 5. [FBC R301.2.1] WIND DESIGN CRITERIA. PROVIDE DESIGN
 PRESSURES FOR WINDOW AND DOOR.
 PAGE 1 OF WINDOW AND DOOR PRODUCT APPROVALS ARE IN
 PERMIT, BUT PLEASE PROVIDE THE FULL PRODUCT APPROVAL
 FOR EACH.
  
 6. [FBC R803.2.3.1]SHEATHING FASTENING.
 SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113)
 PROVIDE PRODUCT APPROVALS FOR ROOFING, OR INDICATE THAT
 THEY WILL BE DEFFERED.
  
 7. [FBC R318.1] TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, ?REGISTERED
 TERMITICIDE.? UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 8. [FBC R107]PROVIDE WALL TYPE DETAIL. I SEE 2X6 WALL
 WITH 19/32 CDX, BUT WHAT ARE THE FINISHES ON INTERIOR
 AND EXTERIOR OVER THE PLYWOOD?
  
 9. [FBC R806]WHAT TYPE OF INSULATION IS BEING INSTALLED
 IN THE NEW ATTIC, AND HOW IS IT VENTED?
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  