2018-08-21 13:17:48 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18070117 |
| REVIEWED: AUGUST 20, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC EB = FBC EXISTING BUILDING |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC R107]PROVIDE SURVEY OF PROPERTY. |
| |
| 2. [FBC AMENDED 107]ADD ROOF PITCH TO PLANS. |
| |
| 3. [FBC AMENDEDWHAT IS EXISTING ROOFING MATERIAL, AND |
| WHAT IS PROPOSED? |
| |
| 4. WHAT ARE THE LOADS ON NEW ROOF? |
| |
| 5. [FBC R301.2.1] WIND DESIGN CRITERIA. PROVIDE DESIGN |
| PRESSURES FOR WINDOW AND DOOR. |
| PAGE 1 OF WINDOW AND DOOR PRODUCT APPROVALS ARE IN |
| PERMIT, BUT PLEASE PROVIDE THE FULL PRODUCT APPROVAL |
| FOR EACH. |
| |
| 6. [FBC R803.2.3.1]SHEATHING FASTENING. |
| SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113) |
| PROVIDE PRODUCT APPROVALS FOR ROOFING, OR INDICATE THAT |
| THEY WILL BE DEFFERED. |
| |
| 7. [FBC R318.1] TERMITE PROTECTION. |
| TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED |
| TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, |
| BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR |
| OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| CONSTRUCTION. SEE SECTION 202, ?REGISTERED |
| TERMITICIDE.? UPON COMPLETION OF THE APPLICATION OF THE |
| TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF |
| COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT |
| BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE |
| FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A |
| COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN |
| TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND |
| LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF |
| AGRICULTURE AND CONSUMER SERVICES.? |
| |
| 8. [FBC R107]PROVIDE WALL TYPE DETAIL. I SEE 2X6 WALL |
| WITH 19/32 CDX, BUT WHAT ARE THE FINISHES ON INTERIOR |
| AND EXTERIOR OVER THE PLYWOOD? |
| |
| 9. [FBC R806]WHAT TYPE OF INSULATION IS BEING INSTALLED |
| IN THE NEW ATTIC, AND HOW IS IT VENTED? |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |