Plan Review Notes For Permit 18070109 |
Permit Number |
18070109 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-09 15:41:19 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18070109 | | 7/9/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) DRYER EXHAUST DUCTS SHALL NOT RUN THROUGH PLENUMS- | | SECTION 504.4 FBC M. | | | | 2) THE KITCHEN HOOD EXHAUST IS PROHIBITED FROM | | CONNECTING TO THE DRYER EXHAUST RISER PER SECTIONS | | 504.1 AND 504.10 (ITEM #12) FBC M. | | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR TH THE NEW | | KITCHEN HOOD AND EXHAUST DUCT | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|