Plan Review Notes For Permit 18070082 |
Permit Number |
18070082 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-07-26 07:26:09 | PROVISO | | COMPONENT & CLADDING DESIGN PRESSURES WERE NOT PROVIDED | | ROOF, STOREFRONT, OH DOOR, AND OTHER PRODUCT APPROVALS | | ARE TO BE SUBMITTED PRIOR TO INSTALLATION. WHEN THEY | | ARE SUBMITTED, PROVIDE A SIGNED AND SEALED LETTER FROM | | THE STRUCTURAL ENGINEER OF RECORD WHICH SPECIFY DESIGN | | PRESSURES, FBC B 1609. | | PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | RECORD PRIOR TO SUBMITTAL. | | |
|