2018-07-05 09:21:43PERMIT # 18070082
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) ADDITIOMAL DETAILS REQUIRED REGARDING NEW "HARD
 CANOPY" TO BE INSTALLED ALONG THE LENGTH OF THE STORE
 FRONT. PLEASE PROVIDE DIMENSIONS AND MATERIAL DETAILS.
 PER NFPA 1, CHAPTER 13:
 13.3.2.6* EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES,
 BALCONIES, DECKS, OR SIMILAR PROJECTIONS. IN BUILDINGS
 PROTECTED THROUGHOUT BY AUTOMATIC SPRINKLERS IN
 ACCORDANCE WITH NFPA 13, AUTOMATIC SPRINKLER PROTECTION
 SHALL BE PROVIDED FOR THE EXTERIOR SPACES IN ACCORDANCE
 WITH 13.3.2.6.
  
 13.3.2.6.1 UNLESS THE REQUIREMENTS OF 13.3.2.6.2,
 13.3.2.6.3, OR 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE
 INSTALLED UNDER EXTERIOR PROJECTIONS EXCEEDING 4 FT
 (1.2 M) IN WIDTH. [13:8.15.7.1]
  
 13.3.2.6.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH
 MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE,
 OR FIRE RETARDANT ?TREATED WOOD AS DEFINED IN NFPA 703.
 [13:8.15.7.2]
  
 13.3.2.6.3 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM BELOW THE EXTERIOR PROJECTIONS OF COMBUSTIBLE
 CONSTRUCTION, PROVIDED THE EXPOSED FINISH MATERIAL ON
 THE EXTERIOR PROJECTIONS ARE NONCOMBUSTIBLE,
 LIMITED-COMBUSTIBLE, OR FIRE RETARDANT ?TREATED WOOD AS
 DEFINED IN NFPA 703, AND THE
 EXTERIOR PROJECTIONS CONTAIN ONLY SPRINKLERED CONCEALED
 SPACES OR ANY OF THE FOLLOWING UNSPRINKLERED
 COMBUSTIBLE CONCEALED SPACES:
 (1) COMBUSTIBLE CONCEALED SPACES FILLED ENTIRELY WITH
 NONCOMBUSTIBLE INSULATION
 (2) LIGHT OR ORDINARY HAZARD OCCUPANCIES WHERE
 NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE CEILINGS ARE
 DIRECTLY ATTACHED TO THE BOTTOM OF SOLID WOOD JOISTS SO
 AS TO CREATE ENCLOSED JOIST SPACES 160 FT3 (4.5 M3) OR
 LESS IN VOLUME, INCLUDING SPACE BELOW INSULATION THAT
 IS LAID DIRECTLY ON TOP OR WITHIN THE
 CEILING JOISTS IN AN OTHERWISE SPRINKLERED ATTIC [SEE
 11.2.3.1.4(4)(D) OF NFPA 13]
 (3) CONCEALED SPACES OVER ISOLATED SMALL EXTERIOR
 PROJECTIONS NOT EXCEEDING 55 FT2 (5.1 M2) IN AREA
 [13:8.15.7.3]
  
 13.3.2.6.4 SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM EXTERIOR EXIT CORRIDORS WHEN THE EXTERIOR WALLS OF
 THE CORRIDOR ARE AT LEAST 50 PERCENT OPEN AND WHEN THE
 CORRIDOR IS ENTIRELY OF NONCOMBUSTIBLE CONSTRUCTION.
 [13:8.15.7.4]
  
 13.3.2.6.5* SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR PROJECTIONS GREATER THAN 2 FT (0.6 M) WIDE
 OVER AREAS WHERE COMBUSTIBLES ARE STORED. [13:8.15.7.5]
  
 13.3.2.6.5.1 THE REQUIREMENT OF 13.3.2.6.5 MAY BE
 OMITTED IF THE SEPARATION OF ROOFS, CANOPIES,
 PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS ARE A MINIMUM OF 5 FT (1.5 M) FROM THE
 SPRINKLERED BUILDING. THIS PROVISION IS EFFECTIVE FOR
 NEW CONSTRUCTION PROJECTS ONLY.
  
 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 3) SHEET A500: THE REQUIRED LOCKING MECHANISM IS NOT
 SPECIFICALLY IDENTIFIED. ENTRY DOORS: THUMB-TURN LOCK
 TO BE EQUIPPED WITH A LOCK/UNLOCK INDICATOR.
  
 4) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
  
  