Plan Review Notes
Plan Review Notes For Permit 18070009
Permit Number 18070009
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-07-12 11:00:051. DIAGRAM NEEDS TO INDICATE CIRCUIT NUMBER THAT
 REPRESENTS THE CALCULATIONS OF CIRCUIT
 2. HIGHLIGHT TYPE OF MODULE BEING INSTALLED IN THE
 EQUIPMENT SPEC PACKET.
 3. DIAGRAM DOESN?T PROVIDE ACCURATE INFO TO REFLECT
 EACH FLOOR PLAN
 EX.1. MISSING SMOKE DETECTOR ON THE 2ND FLOOR
 EX.2. DIAGRAM SHOWS STROBE DEVICE FOR GROUND FLOOR
 INSTEAD OF A MINI HORN
  
 4. WHAT IS THE EDITION OF N.F.P.A 72
  
  