2018-07-12 08:16:18 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1. PROVIDE RESUME FOR THRESHOLD INSPECTOR DAVID R. |
| CARMO, P.E. |
| PROVIDE RESUMES AND COPIES OF LICENSES FOR THRESHOLD |
| INSPECTOR AND ALL PROPOSED INSPECTORS. |
| |
| 2. REDUCED COPY OF PLAN PAGE S100 IS NOT LEGIBLE. ALL |
| DOCUMENTS SUBMITTED FOR REVIEW AND PERMIT MUST COMPLY |
| WITH THE PUBLIC RECORDS LAW. |
| FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| |
| 3. ALL DOCUMENTS SUBMITTED FOR REVIEW BEARING THE NAME |
| AND PROFESSIONAL REGISTRATION NUMBER OF A DESIGN |
| PROFESSIONAL SHALL BEAR AN ORIGINAL SIGNATURE AND SEAL. |
| PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND |
| SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, |
| DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE |
| 61G15-23.001. |
| |
| UPON COMPLETION OF JOB PLEASE PROVIDE THE FOLLOWING |
| STATEMENT: |
| ?TO THE BEST OF MY KNOWLEDGE AND BELIEF, THE |
| CONSTRUCTION OF ALL STRUCTURAL LOAD-BEARING COMPONENTS |
| DESCRIBED IN THE THRESHOLD INSPECTION PLAN COMPLIES |
| WITH THE PERMITTED DOCUMENTS AND THE SPECIALTY SHORING |
| DESIGN PROFESSIONAL ENGINEER HAS ASCERTAINED THAT THE |
| SHORING AND RESHORING CONFORMS WITH THE SHORING AND |
| RESHORING PLANS SUBMITTED TO THE ENFORCEMENT AGENCY?. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |
| |