Plan Review Notes
Plan Review Notes For Permit 18061476
Permit Number 18061476
Review Stop M
Sequence Number 1
Notes
Date Text
2018-07-16 11:36:481ST REVIEW FBC-2017 MECHANICAL
 REVISION #18061476
 MASTER #18040489
 7/1618
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS DM-101 & M-101: PROVIDE COOLING AND HEATING
 CALCULATIONS FOR THE NEW WSHP-1. IT APPEARS BY THE DEMO
 DRAWINGS THAT THIS AREA WAS NEVER FULLY CONDITIONED
 BEFORE- SECTION C403.2.1 FBC EC.
  
 2) M-101: PROVIDE AN ACCESS PANEL FOR THE NEW WSHP-1 IN
 COMPLIANCE WITH SECTION 306.1 FBC M.
  
 3) M-101: PROVIDE A FLORIDA PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE O/A LOUVER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  