Plan Review Notes
Plan Review Notes For Permit 18061452
Permit Number 18061452
Review Stop B
Sequence Number 3
Notes
Date Text
2018-10-03 12:24:3210/03/18 READ E-MAIL FROM GERI SHUBERT.
  
 HAVE A GREAT DAY
 GERI SHUBERT
 DIVERSIFIED ROOFING SOLUTIONS, INC
 450 SOUTH OLD DIXIE HWY #1
 JUPITER, FL 33458
 561-841-5676
  
  
  
  
 THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 NOTE:
 IT IS NOT CLEAR WHY SUBMITTING A TWO STORY WALL
 SECTION. THE ITEMS BELOW ARE THE ONES THAT NEED TO BE
 ADDRESSED. PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS,
 SO WE CAN FINISH PROCESSING THIS PERMIT. NOTE: ROOF TO
 WALL WORK NEED TO BE DONE UNDER A SUBPERMIT. ACCORDING
 TO ROBERT (BROWN (BUILDING OFFICIAL) ROOFING CONTRACTOR
 CAN NOT DO THIS WORK UNLESS LICENSE TO DO SO.
  
  
  
 PLAN REVIEW COMMENTS:
 1- IT LOOKS LIKE THE HOUSE WAS DESIGNED FOR SHINGLES AS
 A ROOF COVERING. PROPOSED ROOFING MATERIAL IS CONCRETE
 TILES. PROVIDE ENGINEERING ANALYSIS SHOWING THAT THE
 EXISTING STRUCTURE IA CAPABLE OF SUPPORTING THE
 ADDITIONAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 2- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY
 WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC.
 706.8 FBC-EXISTING-BUILDING.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 SEC. 706.8:
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 3- NEW FLAT ROOF NOA 15-0622.21 AND ENGINEER RAS 117
 CALCULATIONS SUBMITTED ARE OK. NEED TO PROVIDE TWO
 COPIES OF ENGINEER CALCULATIONS WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 WHEN ENGINEER IS SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NEW COMMENTS:
 4- NEW ROOF TILE PRODUCT APPROVAL WAS SUBMITTED. ONLY
 THE COVER PAGES OF FLORIDA PRODUCT APPROVAL FL7849-R11
 WAS SUBMITTED. NEED TO PROVIDE COMPLETE INSTALLATION
 INSTRUCTIONS FOR SPECIFIC ROOF TILE TO BE INSTALLED.
 AND CLEARLY SPECIFY/MARK ADHESIVE PADDY SIZE AND RIDGE
 MATERIAL TO BE USED. PROVIDE 2 COPIES.
 FAC 61G20-3.001.
  
 5- NEW ROOF TILE ADHESIVE PRODUCT APPROVAL WAS
 SUBMITTED. ONLY THE COVER PAGES OF FLORIDA PRODUCT
 APPROVAL FL6332-R8 WAS SUBMITTED. NEED TO PROVIDE
 COMPLETE INSTALLATION INSTRUCTIONS AND CLEARLY
 SPECIFY/MARK ADHESIVE PADDY SIZE AND RIDGE MATERIAL ON
 PAGES 3 AND 4 OF INSTALLATION INSTRUCTIONS. PROVIDE 2
 COPIES.
 FAC 61G20-3.001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved