Plan Review Notes For Permit 18061434 |
Permit Number |
18061434 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-15 17:45:09 | 08/15/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. ON ISOMETRIC DRAWING WATER CLOSET IS NOT VENTED NEXT | | TO LAUNDRY ROOM IN PAGE S-1, IT MAY BE VENTED BY | | LAUNDRY ROOM. IN MASTER NEEDS TO BE VENTED BETWEEN | | WATER CLOSET AND SHOWER. 2017 FBC R3101.2.1 VENTING | | REQUIRED. EVERY TRAP AND TRAPPED FIXTURE SHALL BE | | VENTED IN ACCORDANCE WITH ONE OF THE VENTING METHODS. | | 2. CLEAN OUT ARE NOT REQUIRED ON VERTICAL PIPE BUT ONLY | | IN HORIZONTAL BUILDING DRAIN. | | | | 3. ROMAN TUB FAUCET WILL REQUIRE A THERMOSTATIC VALVE | | IN A REMOTE LOCATION OR A VALVE THAT HAS A BUILT IN | | DEVICE. 2017 FBC R2713.3 BATHTUB AND WHIRLPOOL BATHTUB | | VALVES. | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|