2018-08-15 17:45:0908/15/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON ISOMETRIC DRAWING WATER CLOSET IS NOT VENTED NEXT
 TO LAUNDRY ROOM IN PAGE S-1, IT MAY BE VENTED BY
 LAUNDRY ROOM. IN MASTER NEEDS TO BE VENTED BETWEEN
 WATER CLOSET AND SHOWER. 2017 FBC R3101.2.1 VENTING
 REQUIRED. EVERY TRAP AND TRAPPED FIXTURE SHALL BE
 VENTED IN ACCORDANCE WITH ONE OF THE VENTING METHODS.
 2. CLEAN OUT ARE NOT REQUIRED ON VERTICAL PIPE BUT ONLY
 IN HORIZONTAL BUILDING DRAIN.
  
 3. ROMAN TUB FAUCET WILL REQUIRE A THERMOSTATIC VALVE
 IN A REMOTE LOCATION OR A VALVE THAT HAS A BUILT IN
 DEVICE. 2017 FBC R2713.3 BATHTUB AND WHIRLPOOL BATHTUB
 VALVES.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  