2018-07-27 08:01:11 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NOTE 13 STATES THAT 50% OF LIGHTING SHALL BE HIGH |
| EFFICACY. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT |
| OF THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES |
| SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT |
| OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| FBC EC C405.1, R404.1 |
| 2. NOTE 21 NEEDS TO BE CORRECTED. FIRST ITEM, ALL |
| RECEPTACLES SHOULD BE TAMPER RESISTANT IF THEY ARE |
| INSTALLED PER NEC 210.52 OR NOT,BASED ON NEC 406.11. |
| SECOND ITEM IS THE AFCI NOTE. THIS MENTIONS RECEPTACLES |
| ONLY, THE SAME FOR THE BLOCK NOTE ON THE PLAN |
| DISCUSSING LAUNDRY AREAS. ALL BRANCH CIRCUITS THAT |
| SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8, 210.12; FBC RE E3902, E4002.14 |
| 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 4. PANEL SCHEDULE SHOWS NUMBER 8 WIRE ON 50 AMP BREAKER |
| FOR THE CU'S, AND NUMBER 6 WIRE ON 60 AMP BREAKER FOR |
| THE AHU'S. ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL |
| WIRING, IS NOT RATED FOR THIS AMPERAGE, RESPECTIVE. |
| PROVIDE CORRECTION. NEC 334.80; FBC RE E3705.4.4 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |