2018-07-30 15:09:24 | 07/30/2018 2ND PLUMBING/GAS REVIEW **DENIED** WITH |
| COMMENTS. |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. YOUR ISOMETRIC DRAWING THE TANKLESS WATER HEATER IS |
| 199 BTU AND ON YOUR TECHNICAL DATA V65E IS 150 BTU, |
| PLEASE CORRECT AD RESIZE YOUR TOTAL LOAD. WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 2. SECOND REQUEST, SUBMIT COMBUSTION AIR CALCULATIONS |
| FOR THE ADDED GAS APPLIANCES. WHERE IS COMBUSTION AIR |
| PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION |
| SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED |
| VENTILATION AIR? THIS WILL BE REVIEWED AS A NEW SYSTEM. |
| 2017 FBC R G2407.9.3. COMBINED COMBUSTION AIR AND |
| VENTILATION AIR SYSTEM. |
| 3. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| DESIGN OF THIS GAS SYSTEM. (CSST, PE PIPE) REFER TO THE |
| 2017 FBC FUEL GAS SECS. G2412.4, G2412.8, G2413.1, |
| G2413.2, & G2413.3. |
| 4. SECOND REQUEST, SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. |
| G2408.1. ( POOL HEATER, RANGE AND DRYER?ECT) |
| 5. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| GAS RES. SEC. G2413.2 AND G2404.3. |
| 6. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1 |
| 7. SHOW SHUTOFF VALVE ON GAS ISOMERIC AT EACH APPLIANCE |
| PLEASE, 2017 FBC FUEL GAS RES. SEC. 409.5, APPLIANCE |
| CONNECTION 2017 FBC FUEL GAS RES. SEC. 404.15, 411. |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |