Plan Review Notes
Plan Review Notes For Permit 18061323
Permit Number 18061323
Review Stop G
Sequence Number 2
Notes
Date Text
2018-07-30 15:09:2407/30/2018 2ND PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. YOUR ISOMETRIC DRAWING THE TANKLESS WATER HEATER IS
 199 BTU AND ON YOUR TECHNICAL DATA V65E IS 150 BTU,
 PLEASE CORRECT AD RESIZE YOUR TOTAL LOAD. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2. SECOND REQUEST, SUBMIT COMBUSTION AIR CALCULATIONS
 FOR THE ADDED GAS APPLIANCES. WHERE IS COMBUSTION AIR
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR? THIS WILL BE REVIEWED AS A NEW SYSTEM.
 2017 FBC R G2407.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
 3. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. (CSST, PE PIPE) REFER TO THE
 2017 FBC FUEL GAS SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, & G2413.3.
 4. SECOND REQUEST, SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC.
 G2408.1. ( POOL HEATER, RANGE AND DRYER?ECT)
 5. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS RES. SEC. G2413.2 AND G2404.3.
 6. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1
 7. SHOW SHUTOFF VALVE ON GAS ISOMERIC AT EACH APPLIANCE
 PLEASE, 2017 FBC FUEL GAS RES. SEC. 409.5, APPLIANCE
 CONNECTION 2017 FBC FUEL GAS RES. SEC. 404.15, 411.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  