 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR THE ADDITIONAL WORK AND EQUIPMENT REVISIONS
 4, 7, 12, 15 TO BE INCLUDED IN REVISION FEE.
  
 PG. E3.1
  
 REVISION 7, 12, 15 NEED TO SUPPLY A NARATIVE FOR THE
 WORK BEING DONE.
  
 NEED CUT SHEETS FOR THE FOLLOWING EQUIPMENT: 110.3
 CAM-LOKS
 ATS
 FM200 KEY SWITCH
  
 NEED TO SUPPLY A NEW LAYOUT FOR THE MAIN ELECTRICLA
 ROOM
  
 L1F, L1G, L1H ARE SHOWN ON PLAN BUT NOT ON RISER.
  
 PLEASE CLARIFY ALL OF THE ABOVE COMMENTS
  
 ADDITIONAL LEIBERT SYSTEM?
  
 WHERE IS ROOM MDF?
  
 PG E3.2, E3.3
  
 NARATIVE FOR THE REVSION 7
  
 BREAK ROOM #210 OUTLETS STILL NOT SHOWN AS GFCI WHERE
 REQUIRED 210.8
  
 E5.1
  
 RISER HAS NEW EQUIPMENT SHOWN MSB2 CUT SHEETS,
  
 CAM LOKS NOT SHOWN ON RISER, PLUS SHOW WIRE SIZES TO
 CAM LOKS.
  
 NEW 75KVA AND NEW PANEL L1????? LOAD NOT SHOWN FOR
 THESE LOADS NOT SHOWN ON PANEL SCHEDULE H1B
  
 E6.1
  
 H1B NO LOADS SHOWN FOR TRANSFORMER AND L1 PANEL, PLEASE
 SHOW WIRE SIZES
  
 RISER FOR MDF???
 WHAT FEEDS IT AND WHAT IS IT FEEDING??? ON SECOND AND
 THIRD FLOOR.
  
 CAN NOT FIND MDF ROOM ON FIRST FLOOR?
  
 E6.2
  
 MSB AND MSB2 SHOW CIRCUITS FOR THE UPS IS THERE ONE OR
 TWO???
  
 WHICH EVER CIRCUIT FEEDS THE TRANSFORMER THAT FEEDS THE
 UPS WILL NEED TO BE LOCAKABLE 450.14
  