2018-07-05 13:59:58 | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | VALUE FOR THE ADDITIONAL WORK AND EQUIPMENT REVISIONS | | 4, 7, 12, 15 TO BE INCLUDED IN REVISION FEE. | | | | PG. E3.1 | | | | REVISION 7, 12, 15 NEED TO SUPPLY A NARATIVE FOR THE | | WORK BEING DONE. | | | | NEED CUT SHEETS FOR THE FOLLOWING EQUIPMENT: 110.3 | | CAM-LOKS | | ATS | | FM200 KEY SWITCH | | | | NEED TO SUPPLY A NEW LAYOUT FOR THE MAIN ELECTRICLA | | ROOM | | | | L1F, L1G, L1H ARE SHOWN ON PLAN BUT NOT ON RISER. | | | | PLEASE CLARIFY ALL OF THE ABOVE COMMENTS | | | | ADDITIONAL LEIBERT SYSTEM? | | | | WHERE IS ROOM MDF? | | | | PG E3.2, E3.3 | | | | NARATIVE FOR THE REVSION 7 | | | | BREAK ROOM #210 OUTLETS STILL NOT SHOWN AS GFCI WHERE | | REQUIRED 210.8 | | | | E5.1 | | | | RISER HAS NEW EQUIPMENT SHOWN MSB2 CUT SHEETS, | | | | CAM LOKS NOT SHOWN ON RISER, PLUS SHOW WIRE SIZES TO | | CAM LOKS. | | | | NEW 75KVA AND NEW PANEL L1????? LOAD NOT SHOWN FOR | | THESE LOADS NOT SHOWN ON PANEL SCHEDULE H1B | | | | E6.1 | | | | H1B NO LOADS SHOWN FOR TRANSFORMER AND L1 PANEL, PLEASE | | SHOW WIRE SIZES | | | | RISER FOR MDF??? | | WHAT FEEDS IT AND WHAT IS IT FEEDING??? ON SECOND AND | | THIRD FLOOR. | | | | CAN NOT FIND MDF ROOM ON FIRST FLOOR? | | | | E6.2 | | | | MSB AND MSB2 SHOW CIRCUITS FOR THE UPS IS THERE ONE OR | | TWO??? | | | | WHICH EVER CIRCUIT FEEDS THE TRANSFORMER THAT FEEDS THE | | UPS WILL NEED TO BE LOCAKABLE 450.14 | | |
|