Plan Review Notes
Plan Review Notes For Permit 18061248
Permit Number 18061248
Review Stop G
Sequence Number 1
Notes
Date Text
2018-07-05 06:48:031) SHOW THE TYPE OF PIPING FOR THE GAS SYSTEM ON THE
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 2)THE EXISTING GAS PLAN ON RECORD WITH THE CITY SHOWS
 THE DEVELOPED LENGTH AS 52 FEET TO THE FARTHEST OUTLET.
 THE SUBMITTED PLAN SHOWS 40 FEET DEVELOPED LENGTH.THE
 52 FEET LENGTH SHALL BE USED FOR THE DESIGN OF THIS
 SYSTEM. 2017 FBCR SEC. G2413.4.1.
 3) THE EXISTING PLAN ON RECORD WITH THE CITY SHOWS CSST
 PIPING OVERHEAD WITHIN THE STRUCTURE. SHOW THIS ON THE
 SUBMITTED PLAN IF IT IS ACTUALLY INSTALLED IN THE
 FIELD.
 4) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE CSST
 AND THE CORRESPONDING EHD NUMBER OF THE CORRUGATED
 STAINLESS STEEL TUBING FOR EACH PIPE SIZE. WPB
 AMENDMENTS TO FBC SEC.107.2.1.
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS AND ALSO
 SOFFIT VENTS IN RELATION TO THE WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE EXISTING GAS PLAN ON FILE WITH THE CITY IS
 DESIGNED ON A PRESSURE DROP OF A 0.5 INCH WATER COLUMN
 YET THE SUBMITTED TABLE IS FOR A 6.0 INCH WATER COLUMN
 PRESSURE DROP.CLARIFY.
 7) INDICATE THE PSI OF THIS SYSTEM ON THE GAS PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved