2018-07-19 08:44:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18061244
 7/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET #2: PLEASE INDICATE WHICH UL LISTED GREASE
 DUCT WILL BE USED IN COMPLIANCE WITH SECTIONS 506.3.1.1
 EXCEPTION, AND 506.3.11.3 FBC M.
  
 2) SUBMIT THE NOA'S FOR THE ROOF FANS, AND PROVIDE
 ENGINEERED DETAILS ON THE PLAN- SECTION 301.15 FBC M.
  
 3) REFER TO SECTION 508.1.1 FBC M MAKEUP AIR
 TEMPERATURE, AND INDICATE HOW COMPLIANCE IS BEING MET.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  