2018-07-19 08:44:07 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18061244 |
| 7/19/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET #2: PLEASE INDICATE WHICH UL LISTED GREASE |
| DUCT WILL BE USED IN COMPLIANCE WITH SECTIONS 506.3.1.1 |
| EXCEPTION, AND 506.3.11.3 FBC M. |
| |
| 2) SUBMIT THE NOA'S FOR THE ROOF FANS, AND PROVIDE |
| ENGINEERED DETAILS ON THE PLAN- SECTION 301.15 FBC M. |
| |
| 3) REFER TO SECTION 508.1.1 FBC M MAKEUP AIR |
| TEMPERATURE, AND INDICATE HOW COMPLIANCE IS BEING MET. |
| |
| THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F |
| (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS |
| OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE |
| HVAC SYSTEM. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |