Plan Review Notes
Plan Review Notes For Permit 18061189
Permit Number 18061189
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-13 16:18:091ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE DIGITAL SIGNATURES ARE MISSING ON PLUMBING PAGES
 THEY SHALL COMPLY WITH FAC 61G15-23.003
  
 2. THE INSIDE WIDTH OF THE SHOWER IS SHOWN AT 3'-2" THE
 CODE REQUIRES 36" EXACT. PER FBC ACC 608.2.3
  
 3. IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE
 WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS
 SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL
 BE INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT
 WALLS. FBC ACC 608.3.3
  
 4. THE CLEAR FLOOR SPACE FOR LAV SHALL COMPLY WITH FBC
 ACC 606.2
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. FBC ACC 604.7
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  