2018-08-13 16:18:09 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE DIGITAL SIGNATURES ARE MISSING ON PLUMBING PAGES |
| THEY SHALL COMPLY WITH FAC 61G15-23.003 |
| |
| 2. THE INSIDE WIDTH OF THE SHOWER IS SHOWN AT 3'-2" THE |
| CODE REQUIRES 36" EXACT. PER FBC ACC 608.2.3 |
| |
| 3. IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB |
| BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE |
| WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS |
| SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL |
| BE INSTALLED 6 INCHES (150 MM) MAXIMUM FROM ADJACENT |
| WALLS. FBC ACC 608.3.3 |
| |
| 4. THE CLEAR FLOOR SPACE FOR LAV SHALL COMPLY WITH FBC |
| ACC 606.2 |
| |
| 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. FBC ACC 604.7 |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |