2018-06-26 12:57:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN A 170 MPH VULT WINDSPEED
 AND EXPOSURE CATEGORY D (CLEAR LAKE). THE FASTENING
 OPTION #4 FOR SYSTEM TYPE A(1) THAT WAS SELECTED ON
 PAGE 9 OF NOA NO. 15-1020.01 HAS A MAXIMUM DESIGN
 PRESSURE OF -60 PSF. THIS DESIGN PRESSURE IS NOT
 ADEQUATE FOR THE PERIMETER AND CORNER ROOF AREAS.
 SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY LIMITATION NUMBER 7 ON PAGE 67 OF THE
 PRODUCT APPROVAL. FBC 107.2.1
  