Plan Review Notes For Permit 18061146 |
Permit Number |
18061146 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-30 12:11:28 | 06/30/2018 PLUMBING 1ST REVIEW**DENIED** | | | | 1) MUST SHOW (TDH) TOTAL DYNAMIC HEAD ON HOW THE | | COMPLETE PIPING SYSTEM WAS SIZED. ANSI/ APSP 7, 15 | | | | 2) PROVIDE MANUFACTURE MAIN DRAIN SPEC'S SHOWING FLOW | | RATE AND THAT IT COMPLIES WITH VGB. FBC 107.2.1 | | | | 3) APPLICATION IS CALLING OUT FOR A HEAT PUMP POOL | | HEATER BUT MANUFACTURE MANUAL PROVIDED IS FOR A GAS | | POOL HEATER. PLEASE CLARIFY. PROVIDE A COMPLETE GAS | | PLAN AND SEPERATE PERMIT APPLICATION IF IN FACT THE | | UNIT IS GOING TO BE GAS. | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] |
|