2018-06-30 12:17:3906/30/2018 GAS 1ST REVIEW**DENIED**
  
 1) PROVIDE COMPLETE GAS POOL HEATER MANUFACTURE
 INSTALLATION MANUAL.SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 2) PROVIDE A COMPLETE GAS PLAN ANS SEPERATE SUB PERMIT
 APPLICATION.
  
  
  