Plan Review Notes
Plan Review Notes For Permit 18061127
Permit Number 18061127
Review Stop P
Sequence Number 1
Notes
Date Text
2018-07-30 17:31:381ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASHING MACHINE SHALL CONNECT SEPARATELY TO THE
 BUILDING DRAIN IT CANNOT DISCHARGE THROUGH THE BATHROOM
 GROUP. PER FBC RES P3108.1
  
 2. THE TUB AND TOILET IN BATH #2 ARE NOT VENTED AND THE
 SHOWER IN MASTER BATH IS NOT VENTED SHALL BE VENTED
 BEFORE CONNECTING TO THE BUILDING DRAIN. PER FBC RES
 P3101.2.1, P3108.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  