Plan Review Notes
Plan Review Notes For Permit 18061127
Permit Number 18061127
Review Stop E
Sequence Number 1
Notes
Date Text
2018-07-08 10:08:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2; FS 471, 481
 2. NOTE 5 OF THE ELECTRICAL NOTES FOR AFCI PROTECTION
 DOES NOT INCLUDE ALL AREAS REQUIRED PER CODE. PER CODE,
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION TO NOTE.
 NEC 210.12; FBC RE E3902.16
 3. LAUNDRY CIRCUIT SHOULD BE CALCULATED AT 1.5 KW, NOT
 1.0 AS SHOWN ON PLAN. PROVIDE CORRECTION. NEC 220.82;
 FBC RE E3602.2
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION FOR SHED. NEC
 210.70(A)(2)(B), FBC RE E3903.3
 7. PLAN STATES THERE IS A GAS RANGE, BUT THE LOAD
 CALCULATION SHOWS AN ELECTRIC RANGE. CORRECT
 DISCREPANCY. IF THERE ARE ANY GAS APPLIANCES, PROVIDE
 CARBON MONOXIDE DETECTOR WITHIN 10 FEET OF ANY ROOM
 USED FOR SLEEPING PURPOSE. WPB FBC 107.2.1; FBC RE
 R15.1
 8. PLAN INCORRECTLY LABELS THE FEEDER TO INTERIOR PANEL
 AS 3 - #1 THHN WITH BOND. WHILE THIS ACCOMPLISHES THE
 BOND FUNCTION REQUIRED, IT ALSO ACCOMPLISHES THE
 GROUNDING REQUIRED AND SHOULD THEREFORE BE LABELED AS
 THE EQUIPMENT GROUNDING CONDUCTOR. THIS EGC SHOULD BE
 SIZED PER NEC 250.122 AND/OR FBC RE E3908.8. PROVIDE
 CORRECT NOMENCLATURE AND PROVIDE SIZE PER CODE. NEC
 250.122; FBC RE E3704.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  