Text |
2018-07-08 10:08:44 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED |
| TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON |
| RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC |
| 107.1, 107.2; FS 471, 481 |
| 2. NOTE 5 OF THE ELECTRICAL NOTES FOR AFCI PROTECTION |
| DOES NOT INCLUDE ALL AREAS REQUIRED PER CODE. PER CODE, |
| ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. PROVIDE CORRECTION TO NOTE. |
| NEC 210.12; FBC RE E3902.16 |
| 3. LAUNDRY CIRCUIT SHOULD BE CALCULATED AT 1.5 KW, NOT |
| 1.0 AS SHOWN ON PLAN. PROVIDE CORRECTION. NEC 220.82; |
| FBC RE E3602.2 |
| 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 6. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| LEVEL ACCESS. PROVIDE CORRECTION FOR SHED. NEC |
| 210.70(A)(2)(B), FBC RE E3903.3 |
| 7. PLAN STATES THERE IS A GAS RANGE, BUT THE LOAD |
| CALCULATION SHOWS AN ELECTRIC RANGE. CORRECT |
| DISCREPANCY. IF THERE ARE ANY GAS APPLIANCES, PROVIDE |
| CARBON MONOXIDE DETECTOR WITHIN 10 FEET OF ANY ROOM |
| USED FOR SLEEPING PURPOSE. WPB FBC 107.2.1; FBC RE |
| R15.1 |
| 8. PLAN INCORRECTLY LABELS THE FEEDER TO INTERIOR PANEL |
| AS 3 - #1 THHN WITH BOND. WHILE THIS ACCOMPLISHES THE |
| BOND FUNCTION REQUIRED, IT ALSO ACCOMPLISHES THE |
| GROUNDING REQUIRED AND SHOULD THEREFORE BE LABELED AS |
| THE EQUIPMENT GROUNDING CONDUCTOR. THIS EGC SHOULD BE |
| SIZED PER NEC 250.122 AND/OR FBC RE E3908.8. PROVIDE |
| CORRECT NOMENCLATURE AND PROVIDE SIZE PER CODE. NEC |
| 250.122; FBC RE E3704.6 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |