Plan Review Notes
Plan Review Notes For Permit 18061127
Permit Number 18061127
Review Stop B
Sequence Number 1
Notes
Date Text
2018-07-26 11:50:51****CORRECTIONS****
 W.P.B. PERMIT: 18061127
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SOIL REPORT DIDN'T UPLOAD IN PROJECT DOX. PLEASE
 UPLOAD SOIL REPORT IN SUPPORTING DOCS FOLDER.
  
 2. [FBC 107.3.5.3] PROVIDE SEDIMENT CONTROL PLAN TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS.
  
 3. OWNER OR OWNERS AGENT TO SIGN ENERGY CALCULATIONS.
  
 4. [FBC R608.8]PROVIDE MINIMUM BEARING ON LINTEL
 SCHEDULE. PROVIDE LINTEL DOCUMENTATION FOR SAFE
 LOADING.
  
 5. [FBC R806.3]IF BLOWN IN INSULATION IS BEING USED,
 HOW WILL YOU PREVENT IT FROM BLOCKING CROSS
 VENTILLATION? SHOW/EXPLAIN ON PLANS A-2.0 WHERE
 INSULATION IS CALLED OUT ON WALL SECTION
 INSULATION WIND BAFFLES, VENTING CHUTES, RAFTER VENTS
 OR INSULATION BAFFLES. KEEP THE BLOWN IN FROM GOING
 INTO THE EAVES.
 6. [FBC R107.3.5.3]CONTINUE WALL SECTION ON A-2.0
 THROUGH ROOF.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  