2018-07-26 11:50:51 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18061127 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. SOIL REPORT DIDN'T UPLOAD IN PROJECT DOX. PLEASE |
| UPLOAD SOIL REPORT IN SUPPORTING DOCS FOLDER. |
| |
| 2. [FBC 107.3.5.3] PROVIDE SEDIMENT CONTROL PLAN TO |
| KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT |
| PROPERTIES AND STORM DRAINS. |
| |
| 3. OWNER OR OWNERS AGENT TO SIGN ENERGY CALCULATIONS. |
| |
| 4. [FBC R608.8]PROVIDE MINIMUM BEARING ON LINTEL |
| SCHEDULE. PROVIDE LINTEL DOCUMENTATION FOR SAFE |
| LOADING. |
| |
| 5. [FBC R806.3]IF BLOWN IN INSULATION IS BEING USED, |
| HOW WILL YOU PREVENT IT FROM BLOCKING CROSS |
| VENTILLATION? SHOW/EXPLAIN ON PLANS A-2.0 WHERE |
| INSULATION IS CALLED OUT ON WALL SECTION |
| INSULATION WIND BAFFLES, VENTING CHUTES, RAFTER VENTS |
| OR INSULATION BAFFLES. KEEP THE BLOWN IN FROM GOING |
| INTO THE EAVES. |
| 6. [FBC R107.3.5.3]CONTINUE WALL SECTION ON A-2.0 |
| THROUGH ROOF. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |