2018-07-31 15:44:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PROVISO TO BE CORRECTED UNDER MAIN
 PERMIT #18040104
  
  
 1. THE NEW 6" SANITARY FROM THE UPPER FLOORS CAN NOT
 DISCHARGE TO THE SUMP PIT IN THE BASEMENT IT SHALL
 CONNECT TO THE GRAVITY SYSTEM CONNECTED TO THE CITY
 TAP. PER FBC PL 712.1
  
 2. THE CONDENSATE LINES FROM THE AC UNITS SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM IT APPEARS TO BE
 DISCHARGING INTO THE SUMP PIT. PER WEST PALM BEACH CITY
 ORDINANCE SEC. 90-126.(5)
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  