Plan Review Notes
Plan Review Notes For Permit 18061114
Permit Number 18061114
Review Stop B
Sequence Number 3
Notes
Date Text
2018-07-19 17:09:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC B 1609
  
 1. THE PRODUCT APPROVAL DOES NOT HAVE PROVISION FOR
 ENHANCED FASTENING
 2. THE ENHANCED FASTENING LETTER FROM THE ENGINEER DOES
 NOT ADDRESS THE PANEL SEAM REQUIREMENT, WHICH AFFECTS
 UPLIFT
 3. ENHANCED FASTENING ENGINEERING IS FOR ZONES 2 AND 3
 PRESSURES (-64, -94.6); -74.9 AND -125.9 ARE REQUIRED
 4. IF THE BUILDING OFFICIAL ELECTS TO ALLOW FOR YOU TO
 UTILIZE ENHANCED FASTENING, HOW WILL YOU DESIGNATE THE
 DIFFERENT ZONES FOR THE INSPECTOR? THIS METHOD OF
 INSTALLATION IS TYPICALLY DONE ON FLAT DECKS BASE
 SHEET; THE BASE SHEET CAN BE MARKED/CHALK LINED. HOW
 WILL YOU ACCOMPLISH THIS ON THE METAL ROOF?
 5. ENGINEERING IS TO BE SIGNED, SEALED, DATED
 ORIGINALS. WE SUGGEST THAT, IF YOU USE AN ENGINEER WHO
 HAS A DIGITAL SEAL, YOU SUBMIT THE APPLICATION
 DIGITALLY. FOR THIS ONE PERMIT, IF IT IS DETERMINED
 THAT ENGINEERING IS ACCEPTABLE (BY B.O.), YOU MAY EMAIL
 THE ORIGINAL TO ME AFTER THE BUILDING REVIEW IS PASSED.
  