Plan Review Notes
Plan Review Notes For Permit 18061114
Permit Number 18061114
Review Stop B
Sequence Number 2
Notes
Date Text
2018-07-07 14:37:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SEE SHEET S4.00; THE ASSEMBLY SELECTED DOES NOT
 APPEARS TO MEET THE DESIGN PRESSURE REQUIREMENTS
 SPECIFIED BY THE ENGINEER, FBC B 1609.
  
 2. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 2ND REVIEW, COMMENTS NOT ADDRESSED.
  
 SEE SHEET S4.00. ENGINEER SPECIFIES PRESSURES AS
 FOLLOWS:
  
 ZONE 1 -30.6
 ZONE 2 -64.0
 ZONE 3 -94.6
  
 THE METAL ROOF ASSEMBLY SELECTED HAS A DP LIMITATION OF
 -60 PSF.
  
  
  
  