Plan Review Notes For Permit 18061114 |
Permit Number |
18061114 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-07-07 14:37:16 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1. SEE SHEET S4.00; THE ASSEMBLY SELECTED DOES NOT | | APPEARS TO MEET THE DESIGN PRESSURE REQUIREMENTS | | SPECIFIED BY THE ENGINEER, FBC B 1609. | | | | 2. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL. | | | | 2ND REVIEW, COMMENTS NOT ADDRESSED. | | | | SEE SHEET S4.00. ENGINEER SPECIFIES PRESSURES AS | | FOLLOWS: | | | | ZONE 1 -30.6 | | ZONE 2 -64.0 | | ZONE 3 -94.6 | | | | THE METAL ROOF ASSEMBLY SELECTED HAS A DP LIMITATION OF | | -60 PSF. | | | | | | | | |
|