2018-07-20 12:47:08****CORRECTIONS****
 W.P.B. PERMIT: 18061061
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5.3]ADD THE CONSTRUCTION TYPE TO PROJECT
 DATA.
  
 2. [FBC R107.2.5]SHEET A-100 REFERS TO SHEET A101 FOR
 EXTENT OF DEMO. PLEASE PROVIDE DEMO SHEET A-101.
 IS THE EXISTING STRUCTURE BEING COMPLETLY DEMOED?
 SEPARATE PERMIT FOR DEMO WILL BE NEEDED.
  
 3. [FBC 107.3.5.3]SECTION 1/S-201 DOESN'T MATCH WHAT
 THE ELEVATIONS SHOW. HOW DOES THE RAISED FLOOR WORK
 WITH SLAB ON GRADE AS SHOWN ON 1/S-210?
  
 4. [FBC 107.3.5.3]HOW IS RAISING THE STRUCTURE 1'-9"
 ACHIEVED? SHOW DETAIL OF HOW EXISTING TIES INTO THE NEW
 FOUNDATION.
  
 5. [FBC 107.3.5.3]IS ALL STUCCO BEING REPLACED? PROVIDE
 DETAIL OF MATERIALS/ATTACHMENT OF STUCCO TO WOOD
 FRAMING AND WHAT HAPPENS AT FOUNDATION.
  
 [FBC 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR
 REVIEW, AND THEN FORWARED TO THE BUILDING
 OFFICIAL INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN. THE DEFERRED SUBMITTAL ITEMS
 SHALL NOT BE INSTALLED UNTIL THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 6. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR WINDOWS
 AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFFERED.
  
 7. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
  
 8. [FBC R408.4]PROVIDE ACCESS TO THE UNDER FLOOR SPACE
 18X24 MINIMUM.
  
 9. [FBC 107.3.5.3]PROVIDE DETAIL OF HOW UNDER FLOOR
 VENTS WORK WITH THE FOUNDATION.
  
 10. [FBC 107.3.5.3]UPDATE CODE REFERENCE TO CURRENT
 CODE ON SHEET S-200 WIND LOAD SCHEDULE.
  
 11. [FBC R803.2.3.1]UPDATE SHEATHING FASTENING ON
 S-201.
 SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113)
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  