2018-07-20 12:47:08 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18061061 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC 107.3.5.3]ADD THE CONSTRUCTION TYPE TO PROJECT |
| DATA. |
| |
| 2. [FBC R107.2.5]SHEET A-100 REFERS TO SHEET A101 FOR |
| EXTENT OF DEMO. PLEASE PROVIDE DEMO SHEET A-101. |
| IS THE EXISTING STRUCTURE BEING COMPLETLY DEMOED? |
| SEPARATE PERMIT FOR DEMO WILL BE NEEDED. |
| |
| 3. [FBC 107.3.5.3]SECTION 1/S-201 DOESN'T MATCH WHAT |
| THE ELEVATIONS SHOW. HOW DOES THE RAISED FLOOR WORK |
| WITH SLAB ON GRADE AS SHOWN ON 1/S-210? |
| |
| 4. [FBC 107.3.5.3]HOW IS RAISING THE STRUCTURE 1'-9" |
| ACHIEVED? SHOW DETAIL OF HOW EXISTING TIES INTO THE NEW |
| FOUNDATION. |
| |
| 5. [FBC 107.3.5.3]IS ALL STUCCO BEING REPLACED? PROVIDE |
| DETAIL OF MATERIALS/ATTACHMENT OF STUCCO TO WOOD |
| FRAMING AND WHAT HAPPENS AT FOUNDATION. |
| |
| [FBC 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR |
| REVIEW, AND THEN FORWARED TO THE BUILDING |
| OFFICIAL INDICATING THAT THE DEFERRED SUBMITTAL |
| DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| CONFORMANCE TO THE DESIGN. THE DEFERRED SUBMITTAL ITEMS |
| SHALL NOT BE INSTALLED UNTIL THE DEFERRED SUBMITTAL |
| DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL. |
| |
| 6. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR WINDOWS |
| AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM |
| DEFFERED. |
| |
| 7. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR |
| ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED. |
| |
| 8. [FBC R408.4]PROVIDE ACCESS TO THE UNDER FLOOR SPACE |
| 18X24 MINIMUM. |
| |
| 9. [FBC 107.3.5.3]PROVIDE DETAIL OF HOW UNDER FLOOR |
| VENTS WORK WITH THE FOUNDATION. |
| |
| 10. [FBC 107.3.5.3]UPDATE CODE REFERENCE TO CURRENT |
| CODE ON SHEET S-200 WIND LOAD SCHEDULE. |
| |
| 11. [FBC R803.2.3.1]UPDATE SHEATHING FASTENING ON |
| S-201. |
| SHEATHING NAILS TO BE RING SHANK RSRS01(2 3/8 X 0.113) |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |